Raycap ProTec ZPN package with T1H-300-3+1-E-F, feed terminal, cable set
The ProTec ZPN T1H overvoltage arrester provides comprehensive protection against lightning strikes and overvoltages in main distribution boards and is suitable for TN-S and TT grid systems. The Raycap ProTec ZPN cable set and the ProAcc ZP-TB feed-in terminal provide reliable, safe connections for modern solar systems. The ProTec ZPN cable set with integrated plug and modem gateway connection ensures a safe power supply, while the ProAcc ZP-TB busbar feed terminal complies with DIN and IEC standards for fast, flexible connection. These accessories support the performance and safety of your photovoltaic system efficiently and sustainably.
Product features
Arrester:
- Lightning surge current (10/350 µs) Iimp: 7.5 kA / 30 kA (L-N)/(N-PE)
- Highest continuous voltage (AC) Uc: 300 V / 305 (L-N)/(N-PE)
- Rated leakage surge current (8/20 µs) In: 20 kA / 80 kA (L-N)/(N-PE)
- Maximum leakage surge current (8/20 µs) Imax: 40 kA / 100 kA (L-N)/(N-PE)
- Dimensions LxWxH: 36 mm x 102.3 mm x 238.7 mm
Terminal:
- Rated current according to IEC 61984 IN: 101 A
- Rated current:: 125 A
- Conductor cross-section: 1.5 - 25 mm² (rigid, stranded) / 1.5 - 16 mm² (flexible)
- Connection technology: Tension clamp connection
- Protection category with cover: IP20
- Dimensions LxWxH: 12.5 mm x 54.3 mm x 220.4 mm
Product advantages
- Tool-free installation – Plug & Play
- Compact design of the over voltage protection & clamp, 48.5 mm in total
- This leaves enough space for further lightning & overvoltage protection components, as well as the power supply for the smart meter & feed-in area